The Hospi-Gard Annunciator may be used with our Room Pressure Monitor to provide both visual and audible warnings at a remote location if the room pressure falls outside preset conditions. The green LED indicates the room is in a "steady-on" condition. However, if an alarm condition occurs, the green LED shuts off and a red LED flashes on, while an audible alarm simultaneously sounds. The acknowledgement button silences the audible alarm, and the red LED continues to flash until the alarm condition is corrected. The Annunciator resets itself once conditions return to normal. The variable time delay may be set to eliminate nuisance alarms caused by short transients. Enclosure Standard 2.75 in. x 4.5 in. aluminum wall cover plate Standard 2.8125 in. deep PVC switch box Box includes four integral clamps, swing arms and ears A 1.25 in. deep box may be substituted by the user.
Display Panel Red and green LED indicators Acknowledgement switch
Electrical External power supply: 7-30 Vdc Maximum supply current: 13 mA
Audible Alarm Alarm potentiometer adjusts from 67 dBA - 73 dBA measured 12 inches from the annunciator
Alarm DelayTime delay potentiometer adjusts from 5 - 45 seconds
Ordering Information Part No. 63338 For additional information,please contact your local representative. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND WITHOUT INCURRING LIABILITY FOR MODIFICATIONS TO EQUIPMENT PREVIOUSLY SOLD. |