Hospi-Gard®
Room Pressure Monitor
The
Hospi-Gard® Room Pressure Monitor installs easily on any wall and
can be used for both positive and negative pressure rooms. The unit performs
reliably at low room pressures and has a sensitivity of 0.001 w.g. (0.25
PA) The green or red status light indicates positive
or negative room pressure. The pressure at which the light changes from
positive to negative can be adjusted from the front panel.
The standard
SPDT relay can be connected to an audible alarm or remote status indicator.
Three analog output signals with ranges from 0-5 Vdc, 0-10 Vdc and 4-20
Vdc are proportional to the room pressure.
SPECIFICATIONS
| Enclosure |
-
Light gray polycarbonate case with clear polycarbonate cover
(NEMA type 13)
- 0.85
in. (21.6 mm) knockout openings for electrical and pressure connections
(three on bottom and three on back)
- 3-point
mounting
- Hinges
from either side, opens 180-degrees
|
|
Display Panel |
-
0.5 in. (12.7 mm) LCD pressure display with 0.001 w.g. resolution
- Light
next to LCD indicates unit of measure in Pascals or Inches
of Water
- Green
positive pressure or red negative pressure indicator lights
|
| Electrical |
- 120
V or 240 V, 50/60 Hz (selector switch)
- 5
Watts
- Connection:
0.75 in.(19.1 mm) terminal strip with #6 screws
|
| Accuracy |
- Reading
within 1% of factory setting
- Alarm
output within 1% of set-point (lights and relay)
|
| Range |
-
0.1 w.g. (25 PA) standard range
|
| Alarm
Output |
- SPDT
relay
- Contacts
rated at 5A at 120V or 4A at 240V
|
| Deadband
|
- Preset
at 5% of range
- Field
adjustable from 1% to 20%
|
| Analog
Output |
- 0
to 5 Vdc, 2.5 V at zero pressure, 2 mA max
- 0
to 10 Vdc, 5 V at zero pressure, 2 mA max
- 4
to 20 Vdc, 12 V at zero pressure, 2 mA max
|
| Temperature
and Humidity |
- 32
- 120 degrees F (0 - 50 degrees C) operating temperature
- 10
- 90% relative humidity operating range
|
| Ordering
Information |
|
For
additional information,
please contact your local Representative or
Distributor.
SPECIFICATIONS
ARE SUBJECT TO CHANGE WITHOUT NOTICE AND WITHOUT INCURRING LIABILITY FOR
MODIFICATIONS TO EQUIPMENT PREVIOUSLY SOLD.
|
|