Hospi-Gard®
Annunciator
The
Hospi-Gard® Annunciator may be used with our Room Pressure
Monitor to provide both visual and audible warnings at a remote location
if the room pressure falls outside preset conditions.
The green
LED indicates the room is in a "steady-on" condition. However,
if an alarm condition occurs, the green LED shuts off and a red LED flashes
on, while an audible alarm simultaneously sounds. The acknowledgement
button silences the audible alarm, and the red LED continues to flash
until the alarm condition is corrected.
The Annunciator
resets itself once conditions return to normal. The variable time delay
may be set to eliminate nuisance alarms caused by short transients.
SPECIFICATIONS
| Enclosure
Standard |
| 2.75
in. x 4.5 in. aluminum wall cover plate Standard 2.8125 in. deep PVC
switch box Box includes four integral clamps, swing arms and ears
A 1.25 in. deep box may be substituted by the user |
| Display
Panel |
| Red
and green LED indicators Acknowledgement switch |
| Electrical |
| External
power supply: 7-30 Vdc Maximum supply current: 13 mA |
| Audible
Alarm |
| Alarm
potentiometer adjusts from 67 dBA - 73 dBA measured 12 inches from
the annunciator |
| Alarm
Delay |
| Time
delay potentiometer adjusts from 5 - 45 seconds |
| Ordering
Information |
| Part
No. 63338 |
For
additional information,
please contact your local Representative or
Distributor.