Hospi-Gard® AirCeil™

SPECIFICATIONS

Motor/Blower Assembly
Two direct drive, continuous duty 128 Watt motors with sealed-for-life bearings and inherent overload protection located on the "clean side" of the filter. Fan, dual inlet, centrifugal blower. The motor/blower assembly is mounted on vibration dampening rubber mounts and designed to provide up to 650 CFM of air at a filter pressure drop from 0.35 to 1.00 inch w.g.
Electrical

Standard 115 V, single phase, 50/60 Hz with 13/16-in. conduit knock-out.

Standard 220 V, 50 Hz with 20.6mm conduit knock-out.

Construction
Welded aluminum filter plenum and blower housing with exterior room-side surface finished in a corrosion resistant polyurethane enamel.
Warranty
Limited one year.
Hospital Applications
  • Negative Pressure Rooms
  • Waiting Rooms
  • Aerosol Pentamidine Treatment
  • Bronchoscopy Rooms
  • Emergency Rooms
  • Sputum Induction
  • Intensive Care Units
  • Renal Dialysis Rooms
Other Applications
  • Clinics
  • Physician Offices
  • Addiction Recovery Centers
  • Nursing Centers
  • Homeless Shelters
  • Correctional Facilities
Options
  • AirCeil™ with UV-C germicidal light, Part No. 11122-002
  • Infared Remote Controller (one required), Part No.63760-002
  • Field Installed UV-C Light Part No. 24375-001
  • Hospital Grade Power Cord, Part No. 10660
  • Carbon Prefilter, Part No. 24376-001
  • 1/4 in.-20 Eyebolts (set of 4), Part No. 62529-001
  • Ceiling Air Diffuser, Part No. 63857
  • 12 in. (305 mm) Flexible Duct, Part No. 63856
  • Room Pressure Monitor, Part No. 63337
  • Annunciator, Part No. 63338

 

Part Number 11122-001
Airflow, CFM (m3/hr) Variable 400 to 650 (680-1105)
Maximum BTU / Hour 875
Power Requirements
Amps @ 115 V / 60 Hz
(230 V/50Hz)
400 CFM: 0.72 Amps
650 CFM: 1.20 Amps
Full Load Amps: 2.25 (1.0)
UL Listed Yes
Dimensions, inches
(millimeters)
A 47.62 (1210)
B 19.5 (496)
C 23.62 (600)
D 3.00 (77)
Unit Weight, lbs.
(kilograms)
85 (38.6)

For additional information,
please contact your local Representative or Distributor.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE AND WITHOUT INCURRING LIABILITY FOR MODIFICATIONS TO EQUIPMENT PREVIOUSLY SOLD.